The building we modelled
We are often asked what IES shows for natural ventilation and
alternative ventilation strategies. The short answer is the e-stack
system provides significant energy savings. But don't take our word
for it let us help you to model your classroom.
We have modelled a typical Manchester classroom.
We've taken the middle floor classroom which is
North facing and therefore gets the least solar gain.
The parameters of the classroom are;
Floor Area: 64m2
Height: 3m
Glazing Area: 9.6m2
Occupancy: 32 people 9am-5pm weekdays with a lunch
break
Heating Setpoint: 18degC 8am-5pm weekdays
Lighting Load: 12W/m2
Additional Equipment: 1000W
The simulations have been run on the Manchester TRY weather file
but you can run a simulation on any weather file by downloading the
IES files from the menu on the right.
Similarly we have run the simulations for a building with good
practice U-values and infiltration rates. The U-values we have used
are in the table, but you can tailor the model to have
constructions exactly like your building. We've also modelled a
room with an exposed concrete soffit which acts as thermal mass,
but you can change this too.
| . |
U Values (W/sqm.K) |
Infiltration |
| Roof |
Ground |
Façade |
Glazing |
ACH |
| Part L minimum |
0.25 |
0.25 |
0.35 |
2.2 |
0.25 |
| Typical Practice |
0.15 |
0.15 |
0.25 |
1.6 |
0.15 |
| Good Practice |
0.15 |
0.15 |
0.15 |
1.3 |
0.1 |
| Passivhaus |
0.1 |
0.1 |
0.1 |
0.8 |
0.025 |
We have modelled four different ventilation strategies;
- e-stack
- Conventional Natural Ventilation
- Mechanical Ventilation with Heat Recovery (MVHR)
- MVHR with opening windows in the summertime
E-stack
The e-stack natural ventilation system uses technology filed for
patent by the University of Cambridge which is designed to ensure a
minimum rate of air change between a building and the exterior...
The e-stack natural ventilation system uses technology filed for
patent by the University of Cambridge which is designed to ensure a
minimum rate of air change between a building and the exterior in
Winter to comply with Part F of the building regulations, whilst
minimizing the heating energy required. This is achieved by mixing
the incoming cold fresh air in Winter with hot interior air prior
to it reaching the occupants. The system ensures that the air
quality remains very high but also that the building is totally
comfortable to avoid the risk of cold draughts which are often
associated with natural ventilation systems.
In warmer weather the system typically operates with higher
ventilation flow rates in order to minimize the risk of
overheating, although it can be used in conjunction with thermally
massive building types to exploit the benefits of passive
night-cooling in which case lower ventilation rates are again
used.
How we've modelled this in IES
When calculating the energy associated with ventilation we think
about 2 components
- The energy required to heat the space
- The fan power required to drive the ventilation.
For e-stack ventilation, in the winter (when external
temperature is less than 16degC) we require fan power to mix the
cold incoming air with warm room air. This fan power is 100W when
providing minimum ventilation of 5l/s/person and 150W when we are
required to boost ventilation to prevent overheating. We also
require heating in the space when external temperatures are very
low, such that room temperature drops below 18degC.
In the summer (when external temperature is greater than 16degC)
e-stack ventilation requires no fan power because, when we open the
low level windows in the room we can rely on natural buoyancy to
drive the ventilation.
Through the use of IES we want to obtain the heating requirement
of the room and the flow rates which are required to keep the room
at an acceptable temperature during the wintertime (ie. the flow
rates which will require fan power).
In our model, e-stack ventilation is modelled as a mechanical
ventilation system with no heat recovery. The way that IES deals
with the cold incoming air is as part of a heat balance with all of
the heat gains within the space, and therefore this in analogous to
the way in which e-stack uses the excess heat in the room. The
mechanical system is set to provide 5l/s/person (ie. 160l/s) during
occupied hours. Boost ventilation is provided by specifying a
'natural ventilation' flow rate which is assigned a profile such
that it operates when room temperature exceeds 25degC during the
occupied day. In our model the flow rate is set a 150l/s but this
should be altered to suit your building, so that overheating is
prevented - meaning that we can meet the BB101 standard of no more
than 120 hours greater than 28degC.
More
Conventional Nat Vent
How conventional natural ventilation works
In the summertime we will assume that natural ventilation is
carried out through the use of opening windows at low level and a
passive stack or...
How conventional natural ventilation works
In the summertime we will assume that natural ventilation is
carried out through the use of opening windows at low level and a
passive stack or opening window at high level. Normally the low
level windows will be inlets and the high level openings will be
outlets.
In order to provide sufficient ventilation in the wintertime to
maintain fresh air levels and prevent overheating, we will continue
to use this upwards displacement ventilation strategy. This means
that by opening windows we are risking subjecting the occupants to
cold draughts and therefore we will need to preheat the incoming
air. This preheat will have to take place for any occupied hours
which are less than 16degC.
How we've modelled this in IES
When calculating the energy associated with ventilation we think
about 2 components
- The energy required to heat the space
- The fan power required to drive the ventilation.
For conventional natural ventilation, we require no fan power
all year round.
In the wintertime (when external temperature is less than
16degC) we need to preheat the incoming air to 16degC before
supplying it to the room. We also need to supply space heating to
the room, in case it is required for morning preheat to achieve a
setpoint of 18degC in the classroom.
Through the use of IES we want to obtain the amount of
preheating energy required to achieve the target temperature for
incoming cold air. We also want to ensure that we are supplying
enough air to the space to prevent overheating in accordance with
BB101.
In our model, natural ventilation is modelled as a mechanical
ventilation system. This is the easiest way to force IES to model a
preheat on incoming air! We will however not attribute any fan
power to supply and extract the air from the space. The mechanical
system is set to provide 5l/s/person (ie. 160l/s) during occupied
hours, but incorporates a boost which is assigned a profile such
that it operates when room temperature exceeds 25degC during the
occupied day. In our model the boost flow rate is set at
150l/s but this should be altered to suit your building, so
that overheating is prevented - meaning that we can meet the BB101
standard of no more than 28 hours greater than 28degC.
More
MVHR
How mechanical ventilation with heat recovery works
The mechanical ventilation system supplies fresh air at minimum
ventilation rate during the wintertime and exceeds minimum
ventilation when...
How mechanical ventilation with heat recovery works
The mechanical ventilation system supplies fresh air at minimum
ventilation rate during the wintertime and exceeds minimum
ventilation when it is necessary to prevent oveheating.
The heat exchanger is set at 50% efficiency, meaning that this
is the maximum amount of heat which can be recovered. However the
supply air is also controlled so that its temperature does not make
the room exceed 21degC and therefore the heat exchanger has a
bypass function which means that we can use a smaller percentage of
heat recovery or no heat recovery at all if the incoming air is of
a sufficient temperature.
How we've modelled this in IES
When calculating the energy associated with ventilation we think
about 2 components
- The energy required to heat the space
- The fan power required to drive the ventilation.
For mechanical ventilation we will operate in the same way
throughout the whole occupied year. The mechanical system is set to
provide minimum ventilation of 5l/s/person (ie. 160l/s) during
occupied hours. Boost ventilation is provided by specifying a
'natural ventilation' flow rate which is assigned a profile such
that it operates when room temperature exceeds 25degC during the
occupied day. In our model the flow rate is set at 150l/s but this
should be altered to suit your building, so that overheating is
prevented - meaning that we can meet the BB101 standard of no more
than 120 hours greater than 28degC.
Heating is provided to the room through radiators in the space
which are set to maintain a room temperature of 18degC during
heating hours.
Through the use of IES we want to obtain the heating requirement
of the room and the flow rates which are required to keep the room
at an acceptable temperature which is the sum of the minimum
ventilation rate, plus any boost ventilation required.
The flow rates will then we translated into a fan power required
to achieve the rate. This is done by using a typical fan curve for
a range of MVHR systems, where minimum ventilation of 160l/s
requires around 160W and the fan power will never exceed 500W,
which we have set as a fixed maximum inspite of the flow rate.
More
MVHR with Opening windows
How mechanical ventilation with heat recovery and opening
windows works
In some buildings a MVHR system is specified which will be used
in the wintertime to reduce the amount of heating which...
How mechanical ventilation with heat recovery and opening
windows works
In some buildings a MVHR system is specified which will be used
in the wintertime to reduce the amount of heating which is required
in the space. However due to the high fan power required in the
summertime to prevent overheating, opening windows will be provided
for natural ventilation during the summer months, when the MVHR
system will be switched off.
However, the likelihood is that the opening windows provided for
the summertime will only be provided on one façade and the amount
of opening area they can provide will be insufficient to prevent
summertime overheating. It is possible that during peak summer days
the system will rely on the fans from the mechanical system in
order to drive more flow through the space to prevent
overheating.
How we've modelled this in IES
When calculating the energy associated with ventilation we think
about 2 components
- The energy required to heat the space
- The fan power required to drive the ventilation.
In order to model this hybrid system, the IES model used is
exactly the same as in the pure MVHR example. It is only when we
come to calculate the required fan power that we take into account
that in the summertime we can achieve some ventilation without the
use of fan power.
Therefore, from IES we still want to obtain the heating
requirement of the room and the flow rates which are required to
keep the room at an acceptable temperature which is the sum of the
minimum ventilation rate, plus any boost ventilation required.
The flow rates will then we translated into a fan power required
to achieve the rate. In the wintertime (when external temperature
is less than16degC) the flow rate will be achieved using the full
mechanical system and therefore the fan power will be calculated
from the fan curve described under MVHR. However, in the summertime
(when external temperature is greater than 16degC), we can provide
240l/s via opening windows and therefore any flow rate required
above and beyond this will be provided mechanically and the fan
power will be calculated for a flow rate which is equivalent to the
total fan power minus 240l/, using the fan curve.
Design Considerations
- Single sided ventilation may not provide ventilation to the
back of the room, causing significant temperature
stratification.
- Using the fan from the MVHR unit may exceed the specific fan
power that is permissible under part L for a localised boost fan
which aids natural ventilation.
More
Conclusions
The energy consumption associated with the choice of ventilation
strategy is obviously dependent upon the occupancy and heat loads
within the space, the U-values of the building and where...
The energy consumption associated with the choice of ventilation
strategy is obviously dependent upon the occupancy and heat loads
within the space, the U-values of the building and where the
building is located.
In the UK, we have looked at the energy consumption, of
buildings built to good practice U-value standards. We can see that
e-stack ventilation uses far less energy than conventional natural
ventilation. The main reasons for this are:
- We use the heat gains in a space rather than wastefully
pre-heating the incoming air with radiators or heating
elements.
- Pre-heating the incoming air in this way adds to the
overheating problem in a typical classroom, which means that the
ventilation rate has to be higher than minimum ventilation. The
extra incoming cold air then requires more pre-heating, wasting
further heating energy.
The high energy bills associated with
natural ventilation have led to many in the industry using
mechanical ventilation with heat recovery as an alternative.
However, we can see that e-stack still saves energy with comparison
with MVHR. The reasons for this are:
- MVHR causes the room to overheat in winter, requiring increased
ventilation rates and therefore fan power.
- Even when MVHR is combined with opening windows the fan power
used in the winter and as a summer boost means that the e-stack
ventilation option is the lowest energy.
We have also run comparisons for buildings
with different U-values. For example for buildings with Passivhaus
U-value standards e-stack is still the lowest energy because of its
lower fan power and the ability to operate at minimum ventilation
for a larger proportion of the time during the winter months.
For most building types e-stack ventilation is the lowest energy
option in the UK. By downloading the IES model on the right, you
can see how significant this energy saving might be for your
building.
More
How to model your own building
Download and open the model. By default the model contains
'Vista' files for a Manchester TRY weather file and Passivhaus and
Good Practice U-value standards.
In order to run your own...
Download and open the model. By default the model contains
'Vista' files for a Manchester TRY weather file and Passivhaus and
Good Practice U-value standards.
In order to run your own simulations there are four main
parameters to change; the occupancy of the room eg. number of
people, the U-values, location and the ventilation strategy.
- Occupancy - This can be changed in Building
Template Manager. By default the occupancy is set to the profile
'School Week Accurate' which runs 9-5pm with 10 minute breaks and
an hour for lunch.
- U-values - the construction database contains
constructions with U-values for Passivhaus, Good Practice, Typical
Practice and Minimum Part L. These can be applied to your building
as necessary.
- Location - This can be set to any location
based on IES standard weather files. As standard the building is in
Manchester.
- Ventilation Strategy - the 3 possible
ventilation strategies are MVHR, e-stack and conventional natural
ventilation. All of these can be found in ApHVAC. As standard the
ventilation will be applied to the north facing, middle storey
classroom, 1_N.
- The ApacheSim simulations can now be run.
- The outputs should now be imported into the excel spreadsheet
to post-process the fan power and to generate a graph of energy
consumption.
- For Conventional Natural Ventilation it is required to output
'Room Heating Plant Sensible Load' and 'ApHVAC heating coils load'.
This sum of these 2 numbers is the total heating energy demand of
that room.
- For all other ventilation modes the outputs required are 'Dry
Bulb Temperature', 'Air Temperature', 'Heating Plant Sensible
Load', 'ApHVAC Air Supply' and 'Natural Vent'. The formulae within
the Excel sheet will use these numbers to calculate the required
fan power and heating energy required for the room.
More
Please click to download the Breathing Buildings IES modelling for natural ventilation
Download